Integra Group | MA-1000A
BRIDGE is a retina multi-purpose WordPress theme built on very powerful and flexible framework by QODE.
agency, ajax, background video, blog, business, clean, creative, fullscreen, mega menu, modern, multi-purpose, parallax, portfolio, responsive, retina
16904
page-template-default,page,page-id-16904,ajax_fade,page_not_loaded,,side_area_uncovered_from_content,qode-child-theme-ver-1.0.0,qode-theme-ver-17.0,qode-theme-bridge,qode_header_in_grid,wpb-js-composer js-comp-ver-5.5.5,vc_responsive
 

MA-1000A

MA-1000A is an intelligent analog addressable fire alarm control panel with a two-loop configuration which supports up to 126 XP95 and Discovery devices or up to 252 Soteria addressable devices per loop, as well as a variety of call points, detectors, interfaces, beacons, and loop sounders.
It has large and is suitable for complex cause-and-effect programming as well as an extensive range of user-controllable functions.

Code MA-1000A
Description AnalogAddressable Fire Alarm Control Panel, UOJZ.S36158
Standards UL864 10th Edition, SII1220 and TR TC EAC 043-2017
Specification
Panel display 4-line x 16-character LCD display, multilingual support
Panel keyboard Full numeric keyboard: Reset, Silence, Forward, ESC, Enter
Panel indication LED indication: AC, Alarm, Trouble, Silence, Supervisory
Sound Internal alarm buzzer
Number of loops 2 SLC loops class A with option of 4-loop class B operation
Loop powered outputs 700 mA power for loop
Addresses per loop Up to 126 XP95 and Discovery analog addressable devices
Up to 252Soteriaanalog addressable devices

Programming port USB port for PC communication
Output ports RS485 and RS232
Network MA-NET network card for RS-485 network for communication of up to 64 panels in a network with global correlation matrix
MA-NET TCP/IP network card for TCP/IP network
LNET/RS-485 for communication up to 32 conventional MB-202, 204 and 208 panels and/or up to 4 remote annunciators MA-1050A per FACP
Event history Buffer for 2,000 events with date and time stamp
as well as10,000 events in MA-Net card buffer

Service Built-in walk test
Power
Input voltage Input 120VAC 3.2A / 230VAC 1.6A; 50/60Hz
Operated voltage 24VDC 6.5A
Battery Two 12V up to 20 Ah
Output
Panel NACs 4 O/P NACs (600mA)
Panel relays alarm (1), trouble (1), programmable (3)
Physical
Environmental operating temperature 0 – 49°C
Humidity (non-condensing) 0 to 93% RH
Physicalconstruction Metal box
Color RAL3000
Weight 7 kg
Ingress protection IP31
Cable entries top (4), right (11), left (2)
Compatibility
Suitable for use with MTech MA Analog Addressable Fire System
MTech MB Conventional Fire System
MA-1050A Remote Annunciator
MA-1000FSCS Smoke Control System
MA-Monitoring Graphical Management Software

 

CERTIFICATE

GOST-R

SII1220-1